DSEP100 | Mains Decoupling Relay
- CONTINUOUS VOLTAGE RATING: 8 V to 35 V Continuous
- CRANKING DROPOUTS: Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
- MAXIMUM OPERATING CURRENT: 360 mA at 12 V, 170 mA at 24 V
- CONTINUOUS VOLTAGE RATING: 85 V to 305 V AC (Ph to N)
- CONTINUOUS FREQUENCY RATING: 3.5 Hz to 75 Hz
- MAXIMUM OPERATING CURRENT: 58 mA at 110 V AC (Ph to N) / 28 mA at 230 V AC (Ph to N)
- VOLTAGE RANGE: 15 V to 333 V AC (Ph to N) / 26 V to 576 V AC (Ph to Ph)
- FREQUENCY RANGE: 3.5 Hz to 75 Hz
- Voltage asymmetry protection.
- Vector shift protection.
- Incorrect phase sequence protection.
- True 3-phase mains (utility) RMS measurement.
- Front panel/PC software configuration.
- SCADA monitoring.
- Alarm reset button.
- Configurable volt free changeover relays (5).
- DIN rail mount.
Call for Quote for international purchases!
Price range: $1,188.99 through $2,197.99
SKU: P100-01
Categories: AVR | DSE, Main Protection Relay
The DSEP100 G59 mains protection relay detects and protects multiple devices that generate power in parallel with a mains (utility) supply. Examples include diesel generators, photovoltaic (solar) installations and wind turbine installations.
The DSEP100 ensures that all mains (utility) failures are detected. When detection takes place the mains (utility) supply is disconnected from the local source in line with international requirements. This removes the risk of power being supplied to an islanded grid.
OVERALL SIZE
157 mm x 95 mm x 67 mm (6.2” x 3.5” x 2.6”)
PANEL CUTOUT SIZE
N/A
MAXIMUM PANEL THICKNESS
N/A
WEIGHT
0.38kg
PRODUCT VARIANTS
P100-01 - P100 Mains (Utility) Decoupling Relay
157 mm x 95 mm x 67 mm (6.2” x 3.5” x 2.6”)
PANEL CUTOUT SIZE
N/A
MAXIMUM PANEL THICKNESS
N/A
WEIGHT
0.38kg
PRODUCT VARIANTS
P100-01 - P100 Mains (Utility) Decoupling Relay
DSEP100
(pdf, 591KB)