AVR R449 | Generic
- Automatic Voltage Regulator | Exact Generic Replacement for R449
- Steady state voltage regulation ± 0.5%
- Short circuit capability: 3 x Irated for 10 seconds (AREP or PMG excitation)
- Voltage sensing: 0-110v Terminals = 95 to 140 volts (50/60 Hz) or 0-220v Terminals = 170 to 260 volts (50/60 Hz) or 0-380v Terminals = 340 to 520 volts (50/60 Hz)
- Response time: Normal (1 sec) for ± 20% voltage variation or Rapid (0.3 sec) for ± 20% voltage variation. Remote voltage adjustment range: ± 5%
[vc_row][vc_column][vc_btn title=”Call for Quote!” style=”flat” shape=”round” color=”turquoise” link=”url:https%3A%2F%2Fnew-pmi.powermasterinc.com%2Fcontact-us%2F|title:Contact-Us||”][/vc_column][/vc_row]
Call for Quote for international purchases!
$93.49
The R449 Voltage Regulator (AVR) delivers closed-loop control of alternator output voltage by regulating the exciter field current. It operates with AREP or PMG excitation systems and comes standard on Leroy-Somer 8100 and 9100 Series alternators, including compatible models such as LSA51.2, LSA53.1 and LSA54.
The R449 AVR provides ±0.5% steady-state voltage regulation, supports short-circuit capability of 3 × rated current for 10 seconds, and accepts multiple voltage-sensing ranges (110 V, 220 V, 380–520 V at 50/60 Hz). You can select a normal response time (1 sec) or rapid response (0.3 sec) for ±20% voltage variations. It also supports ±5% remote voltage adjustment.
The built-in Load Adjustment Module (LAM) automatically reduces voltage by ~15% during load impact when generator speed drops below the preset frequency threshold, improving stability by reducing active load by ~25% until rated speed recovers.
The R449 AVR includes adjustment capabilities for quadrature droop and output voltage, enhancing system performance and compatibility across generator applications.