Original DSE892-01 | Simple Network Management Protocol (SNMP) Gateway

  • CONTINUOUS VOLTAGE RATING: 8 V to 35 V Continuous
    CRANKING DROPOUTS:Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 8 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
  • MAXIMUM OPERATING CURRENT: 200 mA at 12 V / 110 mA at 24 V
  • MAXIMUM STANDBY CURRENT: 150 mA at 12 V / 90 mA at 24 V
  • COMMUNICATIONS: USB (Single DSE Controller)
    RS232 (Single DSE Controller)
    RS485 (Multiple DSE Controllers)
    Ethernet (Multiple DSE Controllers)
    Ethernet SNMP & SMTP
  • Multiple DSE control module compatibility.
  • Communication port status LEDs.
  • DIN rail mount.
  • Plug & socket connections.
  • Auto generated Email/SNMP TRAP messages when control module events and operarting changes take place.
  • Customisable Email/SNMP TRAPs based upon module instrumentation values.
  • Simple Internet browser configuration.

 

 

Call for Quote for international purchases!

$498.99

Add to Wishlist
Add to Wishlist
Compare
SKU: DSE892-01
Categories: Remote Monitoring

The DSE892 connects DSE control modules to external SNMP systems. Once a connection is made full monitoring and control functionality becomes active. The gateway device specialises in monitoring the instrumentation and operating state of the connected DSE control module.

  • SMTP client email.
  • Automatic MIB file generation to ease system integration.
  • Single DSE892 gateways can be connected to multiple control modules.
  • SNMP SET to change controller mode.
  • SNMP GET for instrumentation.
  • SNMP V2 compatibility

 

OVERALL SIZE
85 mm x 149 mm x 51 mm (3.3” x 5.8” x 2.0”)
WEIGHT
0.24kg
PRODUCT VARIANTS
0892-01 - 892 Simple Management Network Protocol (SMNP) Gateway

Select at least 2 products
to compare